MYA Series 40-120kW

3 level IGBT rectifier and inverter

High Efficiency up to 94%

Output PF 1.0

High ambient temperature up to 50 °C

Fault Trace Management

Colorful LED bar


MYA Series 40-120kW

Advanced Technology

● Latest generation IGBT and three level technology
● Dual DSP control for top performance
● Intelligent fan control and redundant design: 15% load can be driven when 2 fans fail and 40% load when 1 fan fails
● Anti-corrosion resistant coating for all PCB boards
● Separate internal air channel which hot air drives directly towards heat sink without distressing the PCB's and other internal sensitive components

Green Power

● AC/AC efficiency up to 94.5% and 30% load up to 94% efficiency reduces heat dissipation and limits power consumption costs
● High input power factor up to 0.99 and low Input THDi: < 3.0% at full load, much less grid pollution and costs
● Intelligent sleep mode which UPS sleep in random keep maximum efficiency and energy saving

Flexible Design

● Colorful 7" touch screen with LED Indicators. ● Main unit display allows to check the information of each UPS status during parallel mode. ● Flexible Network Management: SNMP ● Expanded dry contact kit (4 in 4 out) ● BMS kit for lithium battery communication

MODELMY40AMY50A
MY60AMY80AMY100AMY120A
INPUT 
Voltage (Vac)70-155 (L-N) / 120-268 (L-L)
Frequency (Hz)40~70
Power Factor≥0.99
Phase3φ4W+PE
THDi at full linear load<3%
BYPASS
Bypass Voltage (Vac)208±20%
Frequency Range (Hz)50/60 (±5%/±10%)
Overload≤130%: long run; 130%< load ≤150%: 5min; 150%<   load ≤200%: 1s; 200%< load≤300%: 100ms; >300%: immediately.
OUTPUT
Capacity (kW)40506080100120
Power Factor1 (0.5 leading to 0.5 lagging)
Voltage (Vac)190/200/208/220±1%
Frequency (Hz)50/60±0.1% (Battery mode)
Phase3φ4W+PE
Three Phase Difference≤1%
WaveformPure sine wave, THDv<1% at linear load, THDv<4% at non-linear load
Transfer Time (ms)0
AC-AC Efficiencyup to 94%
Overload101-105% Long run, 106-110% load for 60 minutes, 111%-125% load for 10 minutes, 126%-150% load for 1 minute, over 150%   load transfer to bypass
BATTERY
Battery Voltage (Vdc)±144   (±120~±144 adjustable)
Battery TypeExternal
Charging Current (A) MAX3060
GENERAL
Communication InterfaceRS485, MODBUS, dry contact(RS232, BMS, SNMP, expend dry contact card are optional in  slot)
Display7" touch screen+LED
AlarmAC input abnormal, low battery, overload,  failure
ProtectionOutput short-circuit, overload,   over-temperature, battery low   voltage, output over/low   voltage
Noise (dB)<68
Altitude(m)0-2000 no derate
IP GradeIP20
Working Temperature (°C)0 ~ 40 no derate, 40~50 auto derate.
Relative Humidity0 ~ 95%, no condensation
Dimension (W×D×H)(mm)600×1000×1800
Weight (kg)161260


Show More