KR33 Series 300-1200kVA

·  Computer room

·  Data center

·  Precision instrument

·  Commercial facility

·  Intelligent equipment

·  Telecom system

·  Industry


KR33 Series 300-1200kVA

Advanced Technology

● Three level inverter technology
● Support parallel mode up to 9.6MVA
● External input/output transformer connection

Green Power

● High AC/AC efficiency up to 97%
● ECO mode efficiency up to 99%
● High power factor up to 1
● Low THDi ≤2%

Flexible Design

● Common battery bank sharing in parallel system
● Multiple communication interface
● 3-stage battery charging mode
● Self-load test function without load enables onsite commission
● Common bypass cabinet
● External input and output isolation transformer

ItemsKR33300KR33400KR33500KR33600KR33800KR331000KR331200
INPUT
Rate Voltage380/400/415
Voltage Range228-477 (-40%~+25%)
Phase3Ph+N+PE
Frequency Range (Hz)50/60±10% (±5% settable)
Power Factor≥ 0.99
THDi<3% (linear load)
OUTPUT
Input   Voltage (Vac)380/400/415   (-25%~+20% )
Frequency Range50/60Hz±10% (±5%    optional)
Phase3Ph+N+PE
OUTPUT
Output Voltage (Vac)380/400/415±1%
Frequency (Hz)50/60±0.5%
THDv<1% (linear load), <3% (non-linear load)
PF0.9 (1.0 optional)
Max. Efficiency97%
Phase3Ph+N+PE
Overload110% load for 60 min, 125% load for 10 min, 150% load for 1 min, about 150% will transfer to bypass after 1s
BATTERY
Voltage (Vdc)*480 (12V battery from 32   to 44 cells settable)528 (12V battery from 32 to 48 cells settable)
Charging Current (A)25-10025-200
Battery ManagementSelf-load test function
OTHER
Communication InterfaceRS232, RS485, Dry contact, MODBUS, SNMP (optional)
Display7-inch touch screen+LED
Operating Temperature (℃)-5~40
AlarmInput abnormal, battery low-voltage, output overload, UPS  failure
ProtectionShort-circuit, overload, over-temperature, battery   under voltage, input under voltage
IPIP20
Noise (dB)<75
Altitude (m)1500
Dimension (W×D×H) (mm)1000×900×19501400×900×19501900×900×19503000×900×1950
Weight (kg)750110014502400


Show More