Excellent Performance
■ Max. efficiency up to 99%
■ Bi-directional energy flow, charge and discharge
energy storage devices with one unit
■ Ethernet/IP communication interface, to integrate
into other automation networks
■ Compact footprint, space-saving design due to
excellent mechanical design
High Reliability
■ International top-class brands of major components and redundant design for critical circuits
■ Large allowance for power module, strong protection for short circuit
■ Strengthen PCBs coating: Anti salt spray, anti- corrosion, anti-moisture, anti-dust, etc.
Advanced Technology
■ Full digital control technology, higher data processing accuracy & speed
■ Optimized circuit with highly integrated design to make the performance more stable
■ High switching frequency, Low current ripple and high- voltage quality
■ Advanced parallel expansion technology, single /parallel
system compatible
Items | SPT175K-HM | SPT200K-HM |
---|---|---|
DC input (BAT) | ||
Rated input power | 175kW | 200kW |
DC voltage range | 0-1500Vdc | |
Operating voltage range at full load | 1060Vdc~1500Vdc | 1212Vdc~1500Vdc |
Max. working current | 180A | |
Rated working current | 140A | 150A |
DC buffer function | Yes | |
DC input (Bus) | ||
DC voltage range | 550-1500Vdc | |
Operating voltage range at full load | 1060Vdc~1500Vdc | 1212Vdc~1500Vdc |
Max. working current | 180A | |
Overload capacity | 110% for long term, 120% for 1min (at 45°C) | |
Efficiency | ||
Max. efficiency | 99% | |
General data | ||
Dimension (W×H×D) | 600×266×750mm | |
Weight | ≤75kg | |
IP grade | IP66 | |
Operating temperature | -35~60°C | |
Cooling type | Intelligent air cooling | |
Relative humidity | 0~95% (No condensation) | |
Communication | WIFI, Bluetooth, RS485, CAN, Ethernet | |
Altitude | 4000m (>3000m derating) | |
Display | LED, Web, APP | |
Parallel function | Up to 13 units (Support dual-port parallel expansion) | |
Reverse connection protection | Yes | |
Over-temperature protection | Yes | |
Insulation monitoring | Yes | |
Standards | IEC 62477-1, EN IEC 61000-6-2, EN IEC 61000-6-4 |